On-Delay vs Off-Delay Timer Relays: How to Specify the Sequence

An on-delay timer postpones an output change after its timing condition begins; an off-delay timer postpones the return of an output after its control signal ends. The important purchasing question is what starts, interrupts and resets that timing sequence. Removing the timer’s supply is not always equivalent to removing its control signal. Before choosing an on-delay or off-delay timer relay, compare the complete timing diagram with the machine sequence. This guide uses Asiaon’s AST18 timer families as product references and explains how to specify the behavior without assuming that all timer variants work alike.

Product reference: AST18-A/B product specifications and drawings.

Describe the sequence in events, not product names

Begin with a plain-language statement of what the machine should do. For example, a non-safety process might require an output only after a request has remained present for a chosen interval. Another process might need an output to remain active briefly after its request disappears. Those descriptions establish different timing functions even if the same front-panel delay value appears on both devices.

List the relevant events: supply becomes available, a control input changes, the selected interval expires, the control input changes again and supply disappears. For each event, write the required output state. Include interrupted cycles and rapid repeated commands. This event list is more useful than asking a supplier for a generic timer because it reveals behavior that a product label alone does not describe.

Do not start with terminal numbers copied from another brand or model. Terminal designations and available control inputs depend on the selected timer. Build the functional description first, then map it to the manufacturer’s instructions for the exact order code.

Understand a typical on-delay sequence

In a basic non-retentive on-delay function, a valid timing input starts the interval while the timed output remains in its initial state. If the timing condition remains valid until the interval ends, the output transfers. If that condition disappears too early, the timing cycle normally resets, but the actual diagram remains the deciding document.

Imagine a process request that lasts two seconds when the desired delay is five seconds. A conventional non-retentive on-delay should not complete that five-second interval. If a new request arrives later, it starts a fresh interval rather than adding the earlier two seconds. A retentive function would need a different specification because it can preserve elapsed timing under defined conditions.

These example times illustrate sequence logic only. They are not recommended settings for a machine or statements of a particular AST18 variant’s accuracy. Setpoints must come from the process requirements and the validated timing range of the ordered device.

Understand a typical off-delay sequence

The Johdota timer-relay education guide illustrates the distinction between a continuously supplied timer with a control input and a true power-off-delay function.

A signal-controlled off-delay commonly activates its output when the control signal is present. When that signal is removed, the output remains active for the selected interval and then returns. The timer may still require a continuous power supply to finish this interval. Confusing the supply terminals with the control input is a common reason an intended run-on sequence stops immediately.

A separate power-off-delay design can provide a delayed return after supply removal by using an appropriate internal mechanism or stored energy. That capability must be explicitly specified. Do not assume that an ordinary off-delay timer will continue timing after all power is disconnected merely because its name contains the word off.

A returning command during the delay also needs attention. Depending on the function, it may cancel the pending return, restart a period or be ignored until the current cycle finishes. The correct behavior depends on the process, and the supplier should confirm it using the timing chart rather than a verbal description.

AST18-M multifunction timer relay
AST18-M multifunction timer relay. Original Asiaon product photograph; confirm the exact variant from its documentation.

The AST18-M is a multifunction timer family. Its front controls illustrate why the mode setting belongs in the commissioning record alongside the delay value. A correct time entered under the wrong function can produce the wrong sequence.

Compare the functions with a timing review table

Function Typical sequence Critical check
On-delay Timing condition begins: Output transfers after the interval Check interruption before expiry
Signal-controlled off-delay Control signal ends: Output returns after the interval Confirm continued timer supply
Power-off delay Supply is removed: Delayed return if explicitly supported Verify stored-energy and reset conditions
Multifunction timer Depends on selected mode: Depends on the mode diagram Record mode, range and setpoint
Retrigger behavior A new command arrives during timing: Restart, cancellation or other documented action Test the exact selected function

Basis: application review questions and the linked Asiaon product documentation; no additional product ratings are implied.

The table describes common functional distinctions. It does not claim that every listed behavior is available in every AST18 product. The exact variant’s function chart, supply requirements and reset conditions take priority.

Read supply, trigger and output as separate signals

A timing chart usually shows several horizontal traces. Read each trace independently before relating them. The power trace identifies when the timer can operate. The input trace shows the signal that controls timing when a separate trigger is provided. The output trace shows the resulting contact or electronic output state. The interval marker identifies which transition starts the measured delay.

Watch for a chart that uses an energized output symbol rather than a specific normally open contact. A changeover relay has both normally open and normally closed paths, so the physical circuit behavior depends on which terminals are used. The output relay being energized does not mean that every connected circuit is closed.

Also check what the chart means by reset. It may require a minimum interruption, a specific input transition or removal of supply for a defined duration. If the process produces very short pulses, the input may not recognize them as valid commands. Ask for the relevant input and reset requirements rather than treating every change seen by a controller as a valid timer event.

Separate timing accuracy from setting resolution

A dial scale helps an operator select a nominal interval, but its printed divisions are not a complete accuracy specification. A timer may separately specify setting error, repeatability, supply dependence and temperature dependence. Those terms answer different questions. A device can repeat an interval consistently while still being offset from the intended setting.

For a wide-range timer, choose the range that gives useful adjustment around the required interval. Confirm the units and any multiplier control before testing. A record that says only five is incomplete if the timer can be set in seconds or minutes. Photograph the final controls and write the selected mode, range and setting on the commissioning sheet.

When timing precision matters, measure the actual interval using a suitable test method under representative conditions. Include the response of the output device if the process depends on when a valve or motor actually changes state. The timer’s contact transition and the physical process response are not the same event.

Match the output to the controlled load

The timing function determines when the output changes; the output rating determines what it may switch. Check the load voltage, current, duty and starting behavior separately from the timer supply. A timer powered by a low-voltage control circuit may have contacts switching a different circuit, but the complete design must meet the insulation and installation requirements.

For a contactor or solenoid coil, obtain the applicable inductive switching data and suppression requirements. For a larger load, the timer may operate an appropriately selected intermediate device rather than switching the load directly. Do not interpret the largest current on a product page as a universal rating for every type of equipment.

Suppression can affect the release behavior of a controlled electromagnetic device. If a sequence depends on a short delay between two actions, validate the complete circuit with the intended suppression installed. A bench test with an unloaded indicator lamp does not prove the actual load will release at the same time.

AST18-N multifunction timer relay
AST18-N multifunction timer relay. Original Asiaon product photograph; confirm the exact variant from its documentation.

The AST18-N provides another timer-family reference for comparing available modes and controls. Treat the photo as identification, then use its own documentation to confirm the chosen function. Similar housings do not establish identical timing behavior.

Test the interrupted cases before approving the design

A useful acceptance test covers more than one successful timing cycle. Test a command shorter than the set interval, a command maintained beyond it, a returning command during the delay and a loss of supply at each significant stage. Confirm the expected state after supply returns. These tests help expose restart behavior that may otherwise appear only during a real interruption.

Perform commissioning under a qualified, approved procedure with the machine placed in a controlled condition. The timer must not be relied upon as an isolation device. Follow the applicable electrical work rules before changing wiring, and verify that stored or separate energy sources cannot unexpectedly operate the equipment.

For process sequences that affect safety, use the required safety architecture and validated components. An ordinary timer’s delay setting does not, by itself, establish a safety-rated function. The same caution applies to using a run-on timer where immediate stopping is required by the equipment design.

Specify an AST18 timer with a complete request

Start with the Asiaon AST18-A/B product family or the relevant multifunction family, then provide the event description and desired timing diagram. State the available supply, whether a separate control signal exists, the required interval range, output contact arrangement and controlled load. Include the required response to power loss and to commands arriving during an active delay.

Request the full order code and matching instructions. Ask the supplier to identify any assumptions about maintaining power during off-delay operation. When multiple functions are available, specify how the selected mode will be secured and recorded so that an accidental adjustment is detectable during maintenance.

Keep an approved sample and its measured results with the project documentation. If a substitute timer is proposed later, compare its interrupted-cycle behavior as well as its headline time range. Two products can produce the same normal sequence while behaving differently after a brief power interruption.

Frequently asked questions

Is off-delay the same as timing after power is removed?

Not necessarily. Many off-delay functions are controlled by a separate signal and require the timer supply to remain present. A true power-off-delay function must be identified in the exact product documentation.

Can a multifunction timer replace a single-function timer?

Possibly, but only after checking the supply, input type, output rating, timing diagram and reset behavior. The required mode must be available and reliably configured.

Does a timer contact rating also describe its timing accuracy?

No. Contact rating concerns the switched circuit. Timing accuracy and repeatability are separate characteristics that should be reviewed against the process requirement.

Why does a timer restart unexpectedly?

Potential causes include interrupted supply, an input transition, a selected retrigger function or insufficient reset time. Record the supply and input behavior, then compare it with the manufacturer’s timing chart before replacing the device.

Electrical servicing reference: 29 CFR 1910.333 electrical work practices, Cornell Legal Information Institute. Use the rules and approved procedures applicable to the installation; the relay is not a substitute for verified isolation.

Video: the operating principle behind the checks

RealPars explains the separation between relay control and switched load circuits. Use this background when reading the coil, contact and output diagrams discussed above; it does not specify wiring for an Asiaon model.

Watch What is a Relay System ? on YouTube

Continue planning the relay assembly

For a broader starting point, use our general-purpose relay selection guide. Review latching versus non-latching operation when defining the required state after control power changes, and our overview of general-purpose relay applications and advantages for the role of the control interface.