Liquid Level Monitoring Relay: Filling, Draining and Fault Checks

A liquid level monitoring relay should be selected from the sensing method, liquid properties, required filling or draining sequence, and the response to a failed sensor or lost supply. Start with the actual tank process, then confirm the exact relay version and its approved input arrangement. A controller that detects liquid does not automatically provide dry-running protection, independent overflow protection, or permission for a pump to restart.

Asiaon’s ASL18 liquid level monitoring relay is listed for overliquid or underliquid monitoring. That description establishes its product category, but the ordered version’s connection diagram must establish the sensor arrangement, switching sequence and settings. This guide develops a purchasing and commissioning checklist without assigning undocumented electrode terminals or functions to ASL18.

Separate the level decision from the pump power circuit

Write the required process in plain language before choosing a relay. For a filling tank, the pump may need to start at a lower operating level and stop at an upper operating level. For a draining sump, the required sequence is reversed. An alarm-only installation has another purpose: its output announces a condition while a separate controller decides what equipment should do.

These descriptions are process requirements, not instructions to connect a particular number of probes. Some controllers provide two-point operation, some accept a single switch, and some require external logic to retain state between levels. Verify the specific device before assuming it can implement the sequence. Record whether the output means liquid present, healthy condition, pump permission, or alarm. Those meanings are not interchangeable.

Also draw the boundary between the sensing relay and the motor starter. The level relay’s contacts normally participate in a control circuit whose load must fit the documented contact rating. A photograph of a DIN rail controller does not establish that it can switch a pump motor directly. Review the starter coil, contact duty, electrical protection and control supply together.

Confirm what the sensor actually measures

Conductive sensing depends on an electrical path through the liquid. The USGS guidance on specific conductance explains that conductivity varies with dissolved substances and measurement conditions. A successful test in ordinary tap water therefore does not establish reliable detection in the production liquid, a cleaning solution, or a low-conductivity batch.

Where the ordered controller uses conductive electrodes, obtain the permitted sensitivity or resistance range, electrode arrangement, cable constraints and compatibility information. Where it accepts another input, use that input’s documented requirements instead. Do not convert a switch input into a conductive measurement input simply because both involve two wires. Nor should the tank body be used as a return path unless the approved arrangement expressly allows it.

Harvard’s conductivity demonstration illustrates why liquid composition matters. It supports the measurement principle, not a particular ASL18 sensitivity setting. For procurement, request a representative sample test or written compatibility confirmation for the actual liquid, its temperature range and its expected changes over the operating cycle.

Build a process decision table

Review item Evidence to record Acceptance action
Process sequence Filling, draining or alarm only Write the start and stop conditions
Input compatibility Liquid and sensing arrangement Confirm the exact approved input
Level placement Surface motion, inflow and stopping behavior Review physical positions
Output duty Starter coil or alarm load Check applicable contact documentation
Fault response Lost supply, open sensor and contamination Record observable response
Recovery Return of liquid signal and supply Define independent restart permission

Use the table as an application review record rather than a terminal diagram. The sensing concerns are consistent with the Engineering Institute of Technology’s level measurement notes. The exact controller manual remains the authority for wiring and available functions. Mark every unavailable function explicitly so that external logic or a different device can be specified before installation.

Place detection points around real tank behavior

The chosen operating levels must leave enough room for the process to respond. Consider pump stopping behavior, fluid already moving through the pipe, surface movement near the inlet, and access for maintenance. A detection point positioned in splashing liquid may represent a very different condition from the stable level in the main tank. Mechanical placement and process design need to be reviewed together.

For a conductive arrangement, inspect the possible wet paths beyond the intended liquid surface. Condensation, residue or contamination between conductors can create misleading conditions. An insulating coating can also change what the sensor detects. Treat these as inspection and testing questions; the right remedy depends on the approved probe design and the material being handled.

Record how the installation will be cleaned and how probes will be removed. A controller that works during initial commissioning can become unreliable if its sensing surfaces cannot be inspected without excessive downtime. Ask the maintenance team which deposits actually occur, how frequently the process is washed, and whether replacement probes can be installed at the same level.

Keep level, current and voltage functions distinct

A level input answers a question about the sensing point. It does not prove that a commanded pump is moving liquid. A blocked pipe, closed valve, lost prime or damaged impeller can leave the level sequence abnormal while the electrical command remains correct. Decide which of these conditions the process must detect and how each will be confirmed.

Asiaon’s ASC18 current monitoring relay belongs to a different monitoring category. Current information may form part of a wider process assessment, but its usefulness depends on measured healthy and abnormal operating states. Do not claim that adding current monitoring automatically detects every pump fault or makes the installation suitable for unattended operation.

ASC18 current monitoring relay
ASC18 current monitoring relay. Original Asiaon product photograph; consult the exact ordered version documentation.

Likewise, the ASV18 voltage monitoring relay addresses supply voltage conditions. Voltage, current and level devices can serve complementary purposes only when their signals, output states and recovery behavior are coordinated. Avoid connecting several relay contacts in a chain without documenting why each can remove permission and what conditions allow permission to return.

ASV18 voltage monitoring relay
ASV18 voltage monitoring relay. Original Asiaon product photograph; consult the exact ordered version documentation.

Define the response to faults and interruptions

List the failures that matter to the application: loss of sensor connection, contamination creating an unwanted conductive path, loss of controller supply, a stuck output contact, and loss of the motor starter supply. For each, record the expected indication and the expected equipment response. A simple level controller may not distinguish every failure from a genuine wet or dry state.

If a disconnected probe can look like a low level, determine what that means in the chosen filling or draining sequence. The same apparent condition can be inconvenient in one process and hazardous in another. An independent protective layer may be needed where overflow, dry running or loss of containment has unacceptable consequences. Select that layer from the application risk assessment rather than assuming the ordinary control relay provides it.

Supply restoration deserves its own test. Decide whether the process can resume automatically, whether the operator must acknowledge a fault, and whether the pump starter retains an independent stop condition. The relay’s power-up state must be checked from its documentation and observed during commissioning. Never equate recovery of a level signal with permission to restart machinery.

Commission without improvising live connections

Prepare a written test sequence with the installer and process owner. Identify the exact relay, sensor, terminal drawing and starter circuit before energizing. Qualified personnel should use the site’s isolation and verification procedures. Probe simulation, disconnection tests and supply interruption must follow the device instructions and the approved test method; this article does not authorize touching or bridging live terminals.

Begin by proving indications and output states under controlled conditions. Establish the expected result for each input state and check the actual contact path used by the starter or alarm. Then observe a controlled fill or drain cycle using the actual liquid. Record both the detection event and the final process response, including any continued flow after the pump command changes.

Repeat relevant tests after cleaning, reconnection or a change in liquid formulation. Preserve the results with the commissioning record. If the observed sequence differs from the requirement, stop and resolve the discrepancy rather than relabeling the terminals to fit the outcome. A consistent acceptance record is more useful than a photograph of a powered controller with an illuminated indicator.

Diagnose unstable switching in a useful order

When an installation switches repeatedly near a level, first determine whether the liquid surface itself is crossing the sensing point. Compare the event with inlet flow, pump starts and tank agitation. If the physical level is unstable, changing an electrical setting may hide a placement problem. Document the process conditions before deciding whether a delay or different detection arrangement is appropriate.

Next inspect the sensing circuit using the approved isolated procedure. Check for deposits, moisture paths, damaged cables, loose terminations and incorrect reference connections. Compare the installed cable route with the manufacturer’s limits. Verify that any screening or separation requirements were followed rather than adding an improvised earth connection to a measurement terminal.

Finally compare the electrical output with the starter response. A relay can change state correctly while the downstream circuit fails to operate. Conversely, a starter may drop out because its own supply changes while the level indication remains stable. Logging input state, relay output and final equipment status separately makes these cases easier to distinguish.

Prepare a complete enquiry and maintenance record

An effective enquiry includes the liquid identity, expected conductivity information where relevant, temperature and contamination conditions, tank material, required levels, filling or draining description, and the consequence of a missed detection. Add the proposed sensor, cable length, control supply, output load, enclosure conditions and restart requirement. Ask the supplier to identify the precise ordered version and provide its current documentation.

For handover, retain the approved drawing, actual sensor positions, settings, photographs and acceptance results. Include the inspection method and the circumstances that require retesting, such as a probe replacement or a new cleaning chemical. This makes later service decisions traceable and prevents a replacement controller from being accepted solely because its front panel resembles the original.

Frequently asked questions

Can a liquid level relay detect every liquid?

No. Compatibility depends on its sensing method and the exact input arrangement. For conductive sensing, the actual liquid and expected contamination must suit the documented sensitivity range. Confirm compatibility instead of transferring results from a different water sample.

Can I reverse filling and draining by changing one contact?

Only if the exact controller’s function diagram and the complete control circuit support the required sequence. Changing an output contact does not establish the correct state retention, fault response or restart behavior. Verify the full sequence under controlled conditions.

Does a level relay replace independent overflow protection?

Not automatically. Ordinary level control and protective functions need separate assessment against the application’s consequences. Use an independent protective arrangement when the process design requires it, and document how it is tested.