A time relay range setting and its dial setting answer different questions. The selected range establishes the available timing scale, while the adjustment chooses a value within that scale according to the exact model’s instructions. Confirm the time unit, range, function and adjustment method together before accepting a delay. A pointer position or a large advertised timing span is insufficient to establish the operating time of an installed relay.
For a replacement or a new panel, keep a written setting record and measure the intended event. This guide explains how to turn a timing requirement into a reproducible configuration without confusing range selection, function selection and observed process delay.
Write the requirement as two observable events
“Set the timer to ten seconds” is incomplete until the start and end events are defined. Does the interval begin when supply reaches the timer, when a separate input changes or when another condition clears? Does it end when the relay contact changes, when a contactor responds or when the machine reaches a physical state? Those events can produce different measured intervals.
Write the required sequence in plain language before choosing a function. For example, an approved process might require an output command after a defined control input has remained active for a specified interval. Keep the process requirement separate from the name of a timer mode. The timing diagram for the exact device must match the sequence, including reset and restart behavior.
Read the actual product version before interpreting the controls
The Asiaon AST18-N multifunction time relay page presents multiple timing functions and a broad timing range. Its function, time-setting and ratio-setting drawings are the starting point for a configuration inquiry. They do not justify assuming that every visible knob directly displays seconds or that every order code uses the same control input.
Record the complete model and suffix, supply version, input arrangement and output arrangement. Obtain a legible instruction sheet matching that version. A replacement can have a similar housing and a different function selection method. Keeping the full model in the record prevents a later installer from copying a pointer position onto a different timing scale.
Separate unit, range, adjustment and function
The unit identifies whether a value is expressed in seconds, minutes, hours or another supported unit. The range identifies the timing span selected for use. The adjustment selects the target within the supported scale. The function determines how the timer responds to power, control and reset events. These four pieces belong together on the setting sheet.
Do not assume a universal multiplication rule. Some products use a normalized dial and a range multiplier; others show a direct value or combine selectors in another way. Use the documented method for the exact device. If a label or scanned drawing is ambiguous, request clarification before a production setting is released. Guessing from the dial appearance can create an error by a large time factor.
For an arithmetic illustration only, suppose a documented timer uses a normalized adjustment from zero to one and a selected full-scale interval of 60 seconds. A documented fraction of 0.25 would represent 15 seconds because t = fraction × full-scale interval. This example does not describe an AST18 setting rule. The units remain seconds, and the calculation is valid only when that normalized interpretation is explicitly supported.
Select a useful range for the required setting
Choose among the ranges actually supported by the ordered device. The target should be within the permitted adjustment area and should leave enough practical resolution for the application. Avoid choosing the largest possible span merely because it is available. Equally, do not select a range that puts the requested value outside the permitted scale or depends on forcing an adjustment beyond its stop.
A short requested interval may be hard to set meaningfully on a very long analog scale. That is a usability and verification question, separate from the published accuracy terms. Ask for the setting method and relevant performance definition where the process requires a tight interval. The timer’s overall range does not establish the tolerance of every possible setting.

The Asiaon AST18-A/B single-function time relay is shown as an alternative family for a defined sequence. A single-function choice can simplify the setting record when the required operation is already known. Confirm the ordered function and documented controls; do not assume that changing families preserves the same terminal behavior or reset conditions.
Build a configuration table that another technician can use
The following table is a proposed commissioning record. It provides no universal settings or numerical pass limits. The public scope of IEC 61812-1 covers requirements and tests for time relays and coupling relays. That scope is useful context, but it does not certify the pictured product or replace its instructions.
| Review item | Evidence to record | Acceptance action |
|---|---|---|
| Required sequence | Defined initiating and final events | Match the exact timing diagram |
| Version | Full order code and supply/input details | Use the applicable instructions |
| Unit and range | Selected scale and supported span | Confirm the target lies within allowed adjustment |
| Adjustment | Documented interpretation and final value | Do not guess a multiplication rule |
| Verification | Method, conditions, observations and limits | Measure the specified event |
| Restart | Interrupted-cycle and recovery cases | Record the required and observed behavior |
Add the relevant drawing revision and a clear photograph of the final controls where permitted. A photo helps identify an accidental change, while the written values preserve the unit and interpretation. Neither alone proves that the actual delay is acceptable. Retain the measured result and the defined start and end events with the configuration.
Verify the delay at the correct observation point
A test should measure the event the requirement actually specifies. If the requirement concerns the timer contact, observe the contact transition with suitable equipment under the approved procedure. If the requirement concerns a valve or motor sequence, the complete chain may need a separate process test. Keep those results distinct rather than assigning every downstream delay to the timer.
Record the test instrument, observation method, applied supply condition, configured function and target interval. Define the number of trials and acceptance criteria in advance according to the project requirements. A handheld stopwatch can be useful for a coarse check, but its display resolution and operator response may be unsuitable for a short or tightly controlled interval. Select a method appropriate to the required decision.
When results vary, separate a wrong nominal setting from trial-to-trial variation. Repeatedly turning the adjustment after every cycle can conceal the distinction. First establish what was configured, then collect observations under a controlled procedure. For detailed interpretation of tolerance terminology, use the linked timing-accuracy guide rather than inferring a new accuracy specification from a few trials.
Review changes while the timer is operating
Do not assume that changing a range or mode during a running interval is harmless. Follow the exact product instructions for when controls may be adjusted and how a new selection becomes effective. A device may need a defined reset or power sequence after configuration. Make the required sequence part of the procedure instead of relying on an operator’s memory.
Before making changes, place the equipment in the approved safe condition and consider what the output may command during reconfiguration. Electrical access must follow the applicable isolation process. The US workplace provisions at 29 CFR 1910.333 explain deenergizing and verification requirements. A stopped timer output does not itself establish that the installation is isolated for work.
Check restart behavior after the setting has been established
An interval that is correct during one uninterrupted trial can still behave incorrectly after a power interruption or a changed control input. Include the relevant reset, restart and interrupted-cycle cases in the acceptance procedure. Document whether the application expects a fresh delay, continuation or another defined response, and verify it against the selected function’s timing diagram.

The Asiaon AST18-M multifunction time relay is another family with several functions. Its photograph illustrates why the selected mode needs to be recorded explicitly. Product similarity does not establish interchangeable behavior. Choose it only after matching the required sequence, input type, supply and output arrangement with the applicable documentation.
Troubleshoot a delay that differs from the setting
Begin with the setting record. Confirm that the time unit and selected range match the intended value, then verify the function and trigger event. Check whether the observation includes a downstream device response. These simple distinctions often explain why a process interval seems different from a dial value without requiring an assumption that the timer is defective.
If those items agree, review the supply and input conditions against the instructions. Record any unexpected reset or interruption rather than compensating by changing the dial. A longer setting might make one trial appear correct while hiding an unstable trigger. Change one controlled item at a time and keep the before-and-after observations so the cause remains traceable.
For a replacement, compare the old and new timing diagrams rather than transferring only the old nominal number. A correct ten-second setting on the wrong function remains the wrong configuration. Update the drawing, settings sheet and maintenance instructions together once the reviewed behavior is established.
Prepare a precise inquiry and handover
Send the supplier the required start and end events, target interval, allowed variation, reset behavior, supply and control input details. Ask which exact model, function and setting method meet those conditions. Where the product page combines several performance labels, request definitions instead of treating time deviation, repeatability and setting resolution as interchangeable promises.
At handover, identify who may change the configuration and how a change is recorded. Keep a controlled copy of the final setting sheet with the panel documents. This lets future maintenance reproduce the tested behavior and makes a replacement a documented engineering decision rather than an attempt to match the angle of a knob.
Frequently asked questions
Does the same dial position mean the same delay on every range?
No. The selected unit and range can change how an adjustment is interpreted. Use the exact model’s documented method and verify the result at the defined observation point. A pointer photograph without the range and unit is an incomplete record.
Can a timer’s maximum advertised range be used to calculate every setting?
Only if the instructions explicitly establish that calculation. A product family can contain different ranges, versions and control methods. Confirm the ordered device and selected configuration before applying any multiplier or normalized-dial formula.
What should be recorded after commissioning a time relay?
Record the full order code, function, unit, range, adjustment, input and reset conditions, drawing revision, observation method and measured results. Include the acceptance criteria and a clear final-controls photograph where permitted so another technician can reproduce the approved configuration.
Video: measurement and circuit background
RealPars compares PLC and relay control, including programmable timing. Use the lesson to distinguish a required control sequence from the device implementing it; it does not explain AST18 dial settings or authorize a PLC substitution.
Watch What Are the Advantages PLCs Have over Relay Systems? on YouTube